Modular, reliable and efficient – with fast delivery and installation

EAS designs each AHU to meet and exceed the customized needs of the exact project application. EAS always uses the highest quality materials for construction. EAS AHU’s are all aluminum with a foam core panel and true “No Through Metal.” The company’s innovative design approach and experience provides the most efficient systems while maintaining the best serviceability for maintenance. Designed and constructed off site, EAS AHU’s can be pre-piped, pre-wired and pre-controlled to save installation time, overall cost and to improve the quality and safety of the completed product. AHU’s are shipped directly to the final destination where the EAS team will quickly install the system in a matter of days instead of weeks by having completed much of the trade work prior to shipment and delivery.

Benefits

Pre-Commissioned, Turnkey installation services, Full time installation supervision provided with every unit

Factory leakage and deflection testing standard, Field testing services

Energy Efficient

1/2% leakage at 1.5 times design static pressure

Fans are mounted in the center of the airstream for most efficient airflow, All fans provided with Premium efficient TEFC Motors, Monorails provided in each fan section for fan/motor removal

Industrial grade electrical components and fittings

Plug and play electrical and controls incorporated into design

Features

50+ year AHU casing designed to last the life of the building

Foam core panels with aluminum interior and exterior skin as standard, Foam panels are 94% porous free and do not absorb moisture, Panels are NFPA 90 A & B Compliant

Double gasket doors providing 0% leakage @ 10”wg., True no thru metal NFPA 90 test port provided on each door, 3 Point latching hardware with single locking handle on all doors

3/16” Aluminum safety tread floor throughout, Continuously welded floor seams creating 2” deep pan throughout entire unit, Recessed 8”x 12” floor drains in each access section with welded drain pipe extended to exterior of base

Fully welded casing construction eliminates penetrations in the exterior of the unit, Fully welded aluminum IAQ drain pans triple sloped to prevent standing water

Coil headers piped to exterior of unit casing and provided with flanged connection

Cooling coils provided at 450FPM or less as a standard to prevent moisture carryover